Modbus for Field Technicians
Page 27
12. OLD DEVICE SLOW PROCESSORS LIMITED CAPABILITY
Many older devices have old microprocessors that can't do too much work at
once. Often this microprocessor is used to run the device and handle the
Modbus communication.
It is not uncommon to see device with the following limitations.
* You can only read one data point per message. I.e. length must be 1.
* You must have a delay between sending messages.
13. MODBUS ASCII, JBUS, ENRON AND OTHER VARIANTS
There are several variants of Modbus. They are not interoperable. I.e. A
Modbus RTU master cannot read a Modbus ASCII field device.
ASCII an attempt to make the Modbus message human readable but
encoding the hex value of each byte in ascii. Stupid. Doubles the message
length.
Jbus – Highway robbery. A Modbus RTU variation that allows more than 9999
of each data type to be read. These days most vendors include this in their
RTU drivers so you don’t have to pay extra.
Enron – Came up with a way of carrying other data in the Modbus messages.
They used multiple words to form data objects. Essentially a set of
conventions. Both the client and server must support them.