Modbus for Field Technicians
Page 31
15. MODBUS ON RS232
RS232 requires a minimum of 3 conductors to connect the two devices. Rx, Tx
and Ground.
Some devices implement hardware handshaking. This means that before they
send a message some voltage must be applied to one of the other pins on the
port. If hardware handshaking is active on the device, then you will never get
a response until you bypass it or implement it. We recommend bypassing it
because there are often differences in the ways that vendors implemented it.
Here are typical jumper schemes that can be applied to defeat handshaking.
Connect these pins together on the 9 Pin D-Type connector connected to the
server device.
Pin Function
‘1 DCD
4 DTR
6 DSR
And
Pin Function
‘7 RTS
‘8 CTS
‘9 RI (often omitted)
Comments to this Manuals