4. WHAT ABOUT SCALING IN MODBUS
Modbus does not provide a method for transporting large or Floating Point
numbers or a mechanism for scaling analog values.
A 16 bit word can only contain values in the range 0-65535. Only whole
numbers are permitted.
To work around this many server device manufacturers use multipliers and
document them in their manuals. For example, to report a temperature of
58.5 the device reports a value of 585, and makes a note in the manual that
the master should scale by 10.
This scaling is achieved by adopting a convention between the client and the
server.
What about large numbers > 65535
Modbus does not provide a mechanism but 3 important schemes are widely
used.
Long Integers Two consecutive 16 bit words are interpreted as a 32 bit long
integer.
MK10 values Two consecutive words are used. The 1
st
reports the number
of units and the 2
nd
reports the number of 10,000’s.
Floating Point Numbers Two consecutive words are used and a scheme.
(See section X)
These schemes are conventions and not all servers or clients support them.
The protocol does not identify these big numbers. Only the vendor docs do.
What we mean by this is – if you look at the byte stream in a Modbus