Modbus for Field Technicians
Page 20
10. THERE CAN ONLY BE ONE MASTER ON A MODBUS SERIAL
TRUNK
Modbus is a poll-response type of protocol. A master issues a message. If the
address in the message matches the address of a server device it will respond
(if it can). All other devices remain quiet all the time until they are sent a
message with a matching address. The master must wait long enough to
process the response before sending the next message. If it doesn’t then its
next poll and the response from the previous may overlap.
When Modbus over Ethernet is used, more than one master can poll a server
device for data. The number of queries that a server can process
simultaneously is dependent on several factors does the vendor support
multiple simultaneous socket connections and how many do they allow.
Vendors hardly ever publish this information.